Yellow Cat 6 LAN Cable Zoom

New

Cat 6 LAN Cable with Solid Conductors 305m Pull Box - YELLOW

Part # 007.002.0006

Availability: In Stock

$181.50 inc. GST

FREE SHIPPING ON ORDERS OVER $50

4Cabling

Product Description

Details

4Cabling cable boxes offer quality cable at an affordable price, without cutting any corners. Designed to meet the needs of trades people and the industry, our boxes offer the following benefits:

Features

  • 100% Copper solid-core conductors.
  • Heavy duty easy-pull cable box with reinforced handles.
  • Designed for use in horizontal cabling installations.
  • Australian approved.
  • Exceeds the relevant Australian standards for performance.
  • 3P Tested.
  • ETL Listed.

Specs

  • Colour: Yellow
  • Length: 305m
  • For detailed specifications, please see the attached PDF.

Warranty

1 year limited warranty.

Specifications

Specifications

Part # 007.002.0006
Manufacturer 4Cabling
STANDARD COMPLIANCES

All Proposed Category 6 requirements as per ANSI/TIA/EIA, ISO/IEC, and CENELEC EN Standards.
ANSI/TIA/EIA 568-B.2-1 CAT.6
ISO/IEC 11801 CLASS E, 2nd Edition IEC 61156-6
CENELEC EN 50173-1 CENELEC EN 50288-5-1,CENELEC EN 50288-5-2
Flame Retardancy is verified according to IEC 60332-1-2.
We implemented RoHS compliance for the requirement of European Union issued Directive 2002/95/EC.

CONSTRUCTION & CHARACTERISTICS
Conductor Material/Size Bare Copper/23 AWG
Insulation Material HDPE
Thickness Normal Avg.: 0.22 mm
Diameter Normal: 1.00 mm
Colours Blue/White-Blue Orange/White-Orange
Green/White-Green Brown/White-Brown
Elongation Min. 300%
Tensile Strength Min. 1.682 Kg/mm2
Sheath Material PVC
Thickness Average: 0.50 mm
Diameter 6.3 ± 0.3 mm
Colour Assorted upon request
Elongation Min. 100%
Tensile Strength Min. 1.407 Kg/mm2
Aging at 100°C for 168Hrs Min. elongation retention:50%
Min. tensile strength retention:75%
Marking CAT.6 UTP ISO/IEC 11801 & EN 50288 & TIA/EIA-568-B.2-1
ELT/3P VERIFIED - 23AWGX4P SOLID TYPE CM (UL)
c(UL) E164469XXXXXXM
or as customer request.
Flame Test Burning five times, every time is less than 60
seconds and paper flag can't be burned.
APPROVALS
  • UL/cUL Listed
  • ELT/3P Certified ANSI/TIA/EIA-568-B.2-1 Category 6 testing safety/performance requirements.
APPLICATIONS
  • 000BASE-Tx Gigabit Ethernet
  • 10BASE-T, 100BASE-T Fast Ethernet (IEEE 802.3)
  • 100 VG - AnyLAN(IEEE802.12), 155/622 Mbps ATM
  • 550MHz Broadband Video
  • Voice, T1, ISDN
ELECTRICAL PERFORMANCES
Spark Test 2000 ± 250 V ac
Dielectric Strength 2500 V dc / 3 seconds
Insulation Resistance Test Min. 150 MΩ/Km
Conductor Resistance Max.9.38Ω/100m at 20°C
Resistance Unbalance Max. 2%
Capacitance Unbalance Max. 160 pF/100m
Mutual Capacitance Max. 5600 pF/100m
Impedance 64KHz 125Ω ± 20%
1~250Mhz 100Ω ± 15%
Attenuation &
Near End Cross Talk
Frequency
(MHz)
Attenuation
(db/100meters at
20°C),Max.
NEXT
(dB), Min
Power Sum
(dB), Min
1MHz -- 74.3* 64.0*
4 MHz 3.8* 65.3* 63.3*
10 MHz 6.0* 59.3* 57.3*
16 MHz 7.6* 56.2* 54.2*
20 MHz 8.5* 54.8* 52.8*
31.25 MHz 10.7* 51.9* 49.9*
62.5 MHz 15.5* 47.4* 45.4*
100 MHz 19.9* 44.3* 42.3*
150 MHz 25.3* 41.4* 39.4*
200 MHz 29.2* 39.8* 37.8*
250 MHz 33.0* 38.3* 36.3*

The asterisked (*) values are for information only. The minimum Next coupling loss for any pair combination at room temperature is to be greater than the value determined using the formula:
NEXT(f MHZ) ≥ NEXT(0.772)-15LOG10(f MHZ/0.772)

CONFIGURATION

Reviews

Write Your Own Review

You're reviewing: Cat 6 LAN Cable with Solid Conductors 305m Pull Box - YELLOW